CT for Elect. Watt-Hour Meters AC meters
Toroidal Series

POWER MAGNETICS (OLD) | Back

PDF File PDF File
  • For use in electronic watt-hour meter applications
  • 120/240V 50/60 Hz in single and polyphase applications
  • Class 20/200/320Ampere rating (ANSI 0.2, 0.5)
  • Epoxy or tape wrapped coil protection

FALCO PART
NUMBER
L(H) Tol. FREC. (Hz) Turns Ratio DCR (W) NOM. Irms max (A)
 T50111 35.0 Min. 50 1:1500 46 20
 T75012 238.0 ±30% 50 1:2000 114 50
 T14049 60.0 Min. 120 1:2000 25 200
 T16013 55.0 Min. 120 1:2000 22 320
 T17004 200.0 Min. 60 1:4000 66 640

1. L & DCR tested at Ta= 25°C
2. Turns tolerance is ± 1.0 % typ
3. Operating Temperature Range: -40°C to +85°C